Descrizione
P-Net before 1.0.4 releases the Application Relationship of an RPC session, without the abort procedure, when a fragment of a request has another data representation (endianness) than the first fragment of the call. The application is not told that the Application Relationship is gone, the cyclic data stops, and the resources of the Application Relationship are left referencing a cleared structure. Another host can then connect in its place. A host with ADJACENT network access that has observed the activity UUID of the connection, which is sent in clear in every RPC request, can do this with one PDU.
Come correggere
Priorità: Bassa — correggere con la manutenzione ordinaria. Motivazione: CVSS 6.0, EPSS 0.2% (percentile 9).
Versioni da aggiornare
Il record non riporta ancora i prodotti e le versioni corrette (analisi NVD in corso). Consultare l'advisory del vendor nei riferimenti.
Mitigazioni temporanee
Da applicare solo se non è possibile aggiornare subito:
- Ridurre l'esposizione del componente vulnerabile (segmentazione, accesso solo da reti fidate) finché la patch non è applicata.
Verifica
- Individuare tutti gli asset con il prodotto interessato (inventario, scanner di vulnerabilità, CMDB).
- Confrontare la versione installata con quelle indicate sopra.
- Applicare l'aggiornamento in un ambiente di test, poi in produzione; riavviare i servizi se richiesto.
- Ripetere la scansione per confermare la correzione.